Example # 1
 

Location: Pulp Mill “C” Line Level 2 MCC

Equipment: 323-2350 #Washer Wire Turning Roll MCC AD3-A5

Problem: Ph. 1 is heating at line side of breaker.

Recommendation: Clean, lube, and tighten connections. Remove all oxides from wiring and components.

Rise: 59

 
Repair Comments
 
 