Infrared Thermography Examples
Infrared Thermography Example #1
|
Inspected by KC Sullivan |
|||
| Inspection Date: | 9/28/2015 8:13:47 AM | Location: | West MCC 10-SEC4 |
| Equipment: | 45 ME 203 | Equipment Name: | Pre Dryer Web Stabilizer Supply |
| Exception Temperature: | 324.3°F | Potential Problem: | Phase C is severely overheated a T-lead terminal |
| Recommended Action: | Clean, Lube and tighten connections. Remove all oxides from wiring and components | Repair Priority: | Urgent: Repair ASAP! |
| Emissivity: | 0.91 | Reflected Temperature: | 68.0 °F |
| Camera Manufacturer: | Fluke Thermography | Camera: | Ti32-11120328 (60Hz) |

IR000030.IS2
Delta: 221.9 °F
Main Image Markers
| Name | Temperature | Emissivity |
| Hot | 324.3°F | 0.91 |
| P0 | 102.4°F | 0.91 |