Infrared Thermography Example #2

Inspected by KC Sullivan

Inspection Date: 9/28/2015 7:33:24 AM Location: East MCC
Equipment: 20 MP 190 Equipment Name: Broke Dilution Water Pump
Exception Temperature: 189.7°F Potential Problem: Phase B is heating at line side of breaker.
Recommended Action: Clean, Lube and tighten connections. Remove all oxides from wiring and components. Repair Priority: Moderate: Repair on next scheduled downtime.
Emissivity: 0.91 Reflected Temperature: 68.0 °F
Camera Manufacturer: Fluke Thermography Camera: Ti32-11120328 (60Hz)

 

Infrared Thermography Example 2

IR000026.IS2

 

Delta: 45.7 °F

 

Main Image Markers

Name Temperature Emissivity
Hot 189.7°F 0.91
P0 144.0°F 0.91


 