Infrared Thermography Example #1

Inspected by KC Sullivan

Inspection Date: 9/28/2015  8:13:47 AM Location: West MCC
10-SEC4
Equipment: 45 ME 203 Equipment Name: Pre Dryer Web Stabilizer Supply
Exception Temperature: 324.3°F Potential Problem: Phase C is severely overheated a T-lead terminal
Recommended Action: Clean, Lube and tighten connections. Remove all oxides from wiring and components Repair Priority: Urgent: Repair ASAP!
Emissivity: 0.91 Reflected Temperature: 68.0 °F
Camera Manufacturer: Fluke Thermography Camera: Ti32-11120328 (60Hz)

 

Infrared Thermography Example 1

IR000030.IS2

 

Delta: 221.9 °F

 

Main Image Markers

Name Temperature Emissivity
Hot 324.3°F 0.91
P0 102.4°F 0.91


 