Infrared Thermography Examples

Infrared Thermography Example #3

Inspected by KC Sullivan

Inspection Date: 9/30/2015 6:46:09 AM Location: Water Treatment Plant PDC
MCC-APB-005
Equipment: F-CW-02 Equipment Name: Cooling Tower Fan #2 (South)
Exception Temperature: 156.1°F Potential Problem: Phase B is heating at line side of breaker.
Recommended Action: Clean, lube, and tighten connections. Remove all oxides from wiring and components. Repair Priority: Mild severity: Correct on next scheduled downtime.
Emissivity: 0.91 Reflected Temperature: 68.0 °F
Camera Manufacturer: Fluke Thermography Camera: Ti32-11120328 (60Hz)

 

Infrared Thermography Example 3

IR000036.IS2

 

Delta T: 22.1°F

 

Main Image Markers

Name Temperature Emissivity
Hot 156.1°F 0.91
P0 134.1°F 0.91


 